Work on the operating mechanism should be carried out only when the springs are in discharged condition and the circuit breaker is in open position.

Quarterly Maintenance :

20 E-01 Q Clean the operating mechanism, whenever required.
20 E-02 Q Clean the auxiliary switch contacts.
20 E-03 Q Clean the terminal blocks
20 E-04 Q Tighten the electrical connections.
20 E-05 Q Check gear wheels for any wear and tear, replace, if necessary.
20 E-06 Q Check proper functioning of closing and tripping coil.
20 E-07 Q

If overhauling has been done then check by manual charging operation of closing spring to check that the limit switch contact of closing-coil circuit closes 1-2 mm before the contact in the motor circuit; opens.

20 E-08 Q Check the function of limit switch.
20 E-09 Q Check whether heater is functioning properly.
20 E-10 Q Check that the foundation bolts are properly tightened.

Yearly Maintenance or After Approximately 500 Operations:

20 E-11 Y Check the earthing of operating mechanism cubicle.
20 E-12 Y Replace the parts if wear and tear is more.
20 E-13 Y Gear wheels should be lubricated ensuring that no grease comes into the friction clutch. Wipe off if it is there. Grease 784 is to be used.
20 E-14 Y Apply rust preventing medium on untreated surfaces of iron and steel.
20 E-15 Y Check operation of motor.