Clearance at a Glance

Various clearances required to be maintained as per Indian Electricity Rules and Code of practice etc. during construction of a transmission line are given at appropriate places in various chapters. However, for convenience, the various clearances required to be maintained in the construction of a transmission line at a glance are given in the following table:

TABLE : 24.1

Sr. No. Particulars Units Clearance required to be maintained for
132 KV 220 KV 400 KV
1. Live Metal Clearance
(a) Suspension Towers mm 1525(0°- 25° swing)
1075(25° - 45° swing)
2130 (0° - 20°)
1675 (20° -50")
2600 (V - string)
(b) Tension towers mm 1525 2130 2600
2. Ground Clearance m 6.1 7.0 8.84
3. Mid Span Clearance in 6.1 8.5 9.0
4. Phase to Phase Clearance mm 3900 5130 7000
5. Maximum Shielding Angle 30° 30° 30° 20°
6. Power          Line          Crossing Clearance between Lines m 3.05 (from other lines of 11 KV to 132KV) 4.58 (from other lines of 11 KV to 220 KV) 6.10 (front other lines of 11-KV to 400KV)
7. Clearance Between lines and Tramway Crossing m 3.05 3.05 3.05
8. Clearance from Railway^ Track m 14.60 15.40 17.90
9. Prescribed Corridor for Forest clearance etc. m 27.60 35.00 52.00
10. Minimum    Clearances    from Trees m 4.0 4.6 5.5
11. Clearance  over  Rivers  from HFL
(i) Non Navigable River m 6.1 7.00 8.84
(ii) Navigable River m To be maintained in relation to tallest mast in consolation with navigation authorities
12. Clearances from Buildings
(a) Horizontal m 2.744 3.659 5.489
(b) Vertical m 4.573 5.488 7.318
13. Clearance      over     Telecom­munication lines m 2.745 3.050 4.880