Sr. No. |
Item to be inspected |
Inspection Procedure |
By whom to be insp. |
Action Required |
10-18 Y |
Connections of HV, MV & LV |
Check the tightness of clamps on HV, MV & LV bushing top terminals. |
JE(M) AE(M) EE |
Tighten if loose. |
10-19 Y |
Neutral and earth connection |
Check the tightness of neutral connection of neutral bushing top and all earth strips i.e. from neutral of transformer and also from transformer body. The earth resistance of the solidly grounded neutral should be checked form the top of the neutral bushing terminal itself so that any loose or bad connection in the earth circuit is defected in the form of high earth resistance. |
'' |
|
10-20 Y |
Buchholz relay (i) Main |
Open the cover of main buchholz relay and press the push button provided to observe alarm and tripping. |
" |
If alarm and trip does not occur, check circuits of the relay and rectify the defect. |
|
(ii) OLTC |
-do- |
" |
-do- |
10-21 Y |
Thermometer HVLV MV oil |
Open the cap of thermometer pockets on the top of transformer tank and see that the oil in the pocket is available. |
" |
If no oil or less oil, pour transformer oil in the pocket and replace the cap of thermometer. |
10-22 Y |
Dial Glass of Thermo meter |
The Glass cover of dial type thermometer mounted on transformer main tank may be checked. |
JE(M) AE(M) |
Replace the glass of AE(M) thermometer cover, if broken. |
10-23 Y |
Contact testing of thermometer |
In the dial type thermometer on one side of thermometer a knob has been given for manually operating the thermometer, Operate the thermometer and read the temp of various settings i.e. alarm, fan, starting, pump start, trip etc.
Note: Do not forget to reset the maximum temperature indicator.
|
" |
If the setting are disturbed reset the temperature. If any contact elective, replace it. |
10-24 Y |
Oil |
Take samples of oil about 1/2 lit. each from (i) bottom of tank (ii) bottom of radiator bank and (iii) from OLTC after opening the valves provided at these places.
Note : The samples should be taken in a glass flask having air tight cork and two Nos. glass tubes fitted. The oil during sampling should not come in contact with atmosphere. (Detail procedure can be seen in instruction manual of transformer.
|
" |
if average BDV of the samples is less than 35 KV at 4.0 mm gap of 12.5 mm dia balls, then centrifuge the oil. |
10-25 Y |
Oil level |
(o) The oil level in conservator tank should be checked by reading the indicator of magnetic oil level gauge. The scale has been marked with temperature and the reading must tally to the temperature of oil read by the thermometer. If the oil is less then check for fisual leakage of oil from transformer.
(o) Check oil gauge pointer for free movement.
|
" |
If there is substantial oil loss and leakage, attend the leakage and top up the oil (tested oil) if no leakage is there, then check magnetic oil level gauge & repair/replace it, it found defective. |
10-26 Y |
Oil in bushing |
Record the reading of oil level gauge provided on the top of the bushing (HV. MV. LV) |
" |
If needle or level in glass shows no oil in bushing, check the leakage of oil & if there is leakage take action to prevent it. |
10-27 Y |
Cracks deposit on bushing |
Cracks and dirt deposit on bushing shall be checked thoroughly, cleaning of dirt deposit on bushings is essential. |
" |
Clean the dirt on bushings & check for crack Repair/replace the bushing if needed. |
10-28 Y |
Radiator bank |
The dirt & foreign material deposited on the radiator fins & in between the radiator fins shall be checked Dust and dirt deposits on radiator banks effects the efficiency of the radiator. |
JE(M) |
Clean the Radiators Surface. |
10-29 Y |
Fans and Pumps |
The cooling fans and pumps mounted on the radiators banks & below the radiators banks shall be checked cleanliness & running.
(o) Check IR value motor windings after rainy season.
|
JE(M) AE(M) |
Clean the fans and pumps, oiling & greasing must be done in fans & pumps. The defective bearings may also be changed. Replace the defective and pumps. (o) Dry out if found low. |
10-30 Y |
Main tank & pipe connections |
Main tank, pipe connections to various accessories such as radiator, conservator buchholz relay etc. shall be checked for cleanliness & oil leakage. Gasket joints should be thoroughly checked. |
" |
Clean the main tank and repair pipe connections. Replace the defective joint and gaskets to attend oil leakage. |
10-31 Y |
OLTC contacts |
The contacts of diverter switch should be cleaned. This may be done by carrying out operations of the tap changer from 1 to 17 & 17 to 1 when the transformer is under shutdown.
NOTE : During operation of OLTC, keep the transformer OLTC, master/follower/individual switch on individual, and do not forget to take the tap position back to the same of other T/F while energizing the Transformer.
|
" |
Clean the contacts of OLTC. |
10-32 Y |
Cooling system |
Check the starting of cooling fans and pumps by operating the WTI (Thermometer) and check the starting of fans pumps are running and no abnormal noise is there. |
JE(M) AE(M) EE |
If fans do not start check & rectify the control circuit. If pumps do not start check & rectify the control circuit. Repair/replace the defective fans and pumps if any fan/pump gives abnormal sound replace the bearings & properly lubricate. |
10-33 Y |
OLTC Cubicle & control cubicle |
Open the OLTC cubicles power cubicles & control cubicle & check that all these are water tight & have rubber beading. Check the tightness of connection. Check operation of switches illumination and operation of heater circuits. |
" |
Replace defective rubber beading, defective wires and switches etc. Tighten all the connections. Replace the heater if defective. |
10-34 Y |
OLTC |
Record the counter reading of the tap changer which is visible from outside the cubicle. Check the operation of OLTC. Check oil in gear casing. Check limit switch & cleanliness. |
AE(M) JE(M) |
Find out number of operations from the last oil change or commissioning. If no. is more then 5000 replace the oil. If it has given the service of more than 3 years centrifuge the oil lubricate the gear, clean the finger areas, provide oil in gear casing if less, repair/replace the limit switch and clean the parts. |
10-35 Y |
Fastenings & gasketed joints. |
Thoroughly check the jacketed joints on main tank, pipe connections, radiators, relays etc. for any oil leakage & loose/missing bolts and nuts. |
AE(E) JE(M) |
Tighten all loose bolts and nuts & replace the missing bolt if any. |
10-36 Y |
Valves & Stop Cocks |
The valves have been provided on pipes connecting the main tank and radiators. Stop cocks have been provided for smaller pipes on main tank, check these for operation and leaks. Also ensure the position of these valves and stop cocks. |
" |
Attend the leaks and put the valves in correct position. |
10-37 Y |
Insulation resistance |
Disconnect the connection of HV, MV & LV terminals and record the IR values with 5 KV megger Compare the values with those at the time of commissioning. |
" |
If megger values are poor, find out the cause, and centrifuge the oil. Compare readings with previous values. |
10-38 Y |
Pressure relief device |
Pressure relief device has been provided on a separate pipe connected to the main tank. Check the operation by manually operating the test switch and see it tripping occurs.
(i) For 100 MVA Transformer Yearly.
(ii) For 12.5 to 40 MVA Transformer once in 5 years.
|
" |
Replace the pressure relief device if defective. |
10-39 Y |
Dissolved Gas Analysis of oil |
Take out oil samples from valve provided in bottom of Main tank, radiator bank and OLTC and get the dissolved gas and chemical analysis done, Compare the results with those given below.
(1) Dissolved gas Analysis (Recommended) values as per SE 400 KV s/s Design Circle Lucknow letter No. 595/400 KV/ESDC/dated. 21.8.1985.
|
" |
|
|
|
Drying out of transformers is to be done if low iR value is observed. However,
|
10-40 TH |
|
- All power transformers upto 40 MVA capacity should be centrifuged to improve IR value and BDV of oil after every 3 years of service.
|
10-41 F |
|
- All power transformers more then 40 MVA capacity should be centrifuged after every 5 years of service.
|